Sensor Types
                                
                                
                                    RTD input - See full data sheet
                                
                             
                            
                                
                                    Sensor configuration
                                
                                
                                    2 wire, 3 wire, or 4 wire
                                
                             
                            
                                
                                    Full scale signal range
                                
                                
                                    See Full Data Sheet
                                
                             
                            
                                
                                    Accuracy
                                
                                
                                    See Full Data Sheet
                                
                             
                            
                                
                                    Repeatability
                                
                                
                                    0.05% of span
                                
                             
                            
                                
                                    Resolution
                                
                                
                                    24 Bit A/D converter / Depends upon the sensor type
                                
                             
                            
                                
                                    Calibration
                                
                                
                                    None required
                                
                             
                            
                                
                                    Sensor Excitation Current
                                
                                
                                    0.5 mA in 2-wire and 4 wire configurations, 0.25 mA in 3-wire
                                
                             
                            
                                
                                    Isolation
                                
                                
                                    Each sensor galvanically isolated and factory tested to 1000 VDC
                                
                             
                            
                                
                                    Open sensor detection
                                
                                
                                    Yes
                                
                             
                            
                                
                                    CHARM Power Req.
                                
                                
                                    18 mA max @ 24 VDC
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    0.30 W
                                
                             
                            
                                
                                    DC/50/60 Hz Common mode rejection
                                
                                