Sensor Types
                                
                                
                                    NAMUR Sensors, Dry Contacts, Dry contact with end of line resistance
                                
                             
                            
                                
                                    Detection Level for On
                                
                                
                                    > 2.1 mA (<4 kΩ)
                                
                             
                            
                                
                                    Detection Level for Off
                                
                                
                                    < 1.2 mA (>9 kΩ)
                                
                             
                            
                                
                                    Channel Impedance
                                
                                
                                    1.5 kΩ (approximate)
                                
                             
                            
                                
                                    Wetting Voltage
                                
                                
                                    12 Volts (± 5%)
                                
                             
                            
                                
                                    Field Circuit Protection
                                
                                
                                    8 mA Current Limiting Circuit, Field wiring disconnect
                                
                             
                            
                                
                                    CHARM Power Req.
                                
                                
                                    28 mA max @ 24 V DC
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    0.51 W
                                
                             
                            
                                
                                    Fault Detection Capable
                                
                                
                                    Guaranteed short circuit: <100 Ω, Guaranteed good status: 400 Ω to 40 kΩ, Guaranteed open circuit: > 75 kΩ
                                
                             
                            
                                
                                    Configurable Channel Types
                                
                                
                                    Discrete Input - Dry contact or discrete state sensor changing <2 Hz, Pulse Count - Pulse train 0.1 Hz to 10 KHz, 50 µsec min pulse width